Intelligent Monitoring and Control Terminal
Collects and displays data on closing and trip coils, energy storage motors, circuit breaker travel, and in-cabinet temperature and humidity via serial and Ethernet connections. Supports real-time equipment condition monitoring, local operation, data storage, and remote data transmission.
General Specifications
Intelligent Terminal general specifications
| Category |
Parameter |
Specification |
| Mechanical |
Dimensions |
170 × 140 × 64 mm |
| Mechanical |
Weight |
1.3 kg |
| Environmental |
Operating conditions |
0 to +45 °C; relative humidity below 90% |
| Environmental |
Storage conditions |
-20 to +50 °C; relative humidity below 95% |
| Power supply |
Input voltage |
85–305 V AC / 100–430 V DC |
| Power supply |
Power consumption |
15 W |
| Storage |
Media type |
SD card |
| Storage |
Capacity |
Internal: 128 MB; external: 8 GB |
| Display |
Screen size |
10.1 in. |
| Display |
Resolution |
1024 × 600 pixels |
| Display |
Color depth |
65K colors; 16-bit RGB |
| Communications |
Interfaces |
Serial and Ethernet |
Standards and Safety Ratings
Intelligent Terminal standards and safety ratings
| Parameter |
Specification |
| Compliance standards |
GB 4793.1-2007 / IEC 61010-1:2001 Safety requirements for electrical equipment for measurement, control, and laboratory use – Part 1: General requirements |
| Measurement category ratings |
CAT III 1000 V / CAT IV 600 V |
Key Functions
Intelligent Terminal key functions
| Function |
Capabilities |
| Electrical monitoring |
Monitor voltage, current, and power on phases A, B, and C in real time. Record when the main circuit is energized and de-energized. Display voltage and current trends. |
| Closing status |
Display operating characteristic curves and operating times for the trip coil, closing coil, and spring-charging motor. |
| Temperature and humidity monitoring |
Monitor closing-coil and busbar temperatures. Monitor temperature and humidity in the primary and secondary compartments. |
| Mechanical characteristics |
Display the trip-coil rotation angle in real time and convert it to a travel value. Display trip-coil characteristic curves and opening and closing speeds. |
| Historical records |
Select and review stored opening and closing operation records. Select record files from different times and operating states. |
Measurement Specifications
Intelligent Terminal measurement specifications
| Parameter |
Resolution |
Measurement range |
Accuracy |
| Three-phase RMS voltage |
1 V |
1–300 V |
1% |
| Three-phase RMS current |
0.1 A |
0–5 A |
1% |
| Power |
1 W |
0–3000 W |
1% |
| Trip and closing coil current |
0.1 A |
0–2 A |
1% |
| Spring-charging motor current |
0.1 A |
0–15 A |
1% |
| Temperature |
1 °C |
-25 to +150 °C |
1% |
| Relative humidity |
1% |
0–99% RH |
1% |
| Angle |
1° |
0–360° |
1% |